CPSC, Notifier Announce Recall for Fire Alarm Panels
This recall was issued October 30, 2003.
- Company
- Notifier, Of Northford, Conn.
- Posted
- October 30, 2003
- Recall Number
- 04508
- Quantity
- 6,000
- Official Source
- View on CPSC website ↗
Reason for Recall
The AEU can enter a "sleep" mode, where it does not communicate with the system. When this occurs, audible evacuation signals associated with the failed AEU will not operate and building occupants may not be warned of an emergency.
Action Taken
Notifier will provide an upgraded CPU firmware set for each AM2020 and AFP1010 panel, at no charge.
Product Images
Incidents & Injuries
Notifier has received eight reports of trouble signals alarming. In each case the problem was identified and corrected. No injuries have been reported.